Skip Navigation

Replacement of the Australian Standard for Maintenance

Advisory Note

October, 2005

The amended version of AS1851 - Maintenance of Fire Protection Equipment was published in September 2005. This new Standard replaces the previous AS1851
suite of Australian Standards. Apart from consolidating the Standards suite into a single document there are broadly two significant changes.

The first is a more rigorous testing regime at longer intervals than the previous Standard, and the second is the introduction of an annual survey of selected systems.

Testing Regime

The frequency of the tests for both sprinklers and pumps has changed. Generally, the scope for the monthly tests has increased substantially. The monthly scope includes both the current weekly scope and a majority of the current Standard’s quarterly scope.

The new Standard allows the omission of weekly testing of sprinkler systems where:

Weekly testing of pump systems may be omitted where:

It should be noted that the omission of the weekly test could lead to water savings in excess of 50% compared to typical current annual testing consumption in some buildings.

Annual Survey

The second significant change is the introduction of a periodic visual survey of selected systems to assist in maintaining the design intent.

The new version of AS1851 is not called up in the Building Code of Australia. In Victoria, for existing buildings, constructed post July 1994, the required maintenance Standard should be referenced on the Occupancy Permit. If a building owner wishes to change to the new Standard they must either apply to the Relevant Building Surveyor to make the amendment or apply to Council. For Victorian buildings constructed pre July 1994 the owner is required to ensure that the system is "maintained in a state which enables the (system) to fulfill its purpose". For pre 1994 buildings there is no legislative process currently in place that requires the approval of an authority to change the referenced Standard.

The new standard also presupposes a number of design records and hardware that may not exist for older buildings and some that are not even required in the current installation standards. As such, a detailed review of the installation and records should be undertaken prior to adopting the new standard.

The new AS1851 Standard can be purchased from www.standards.com.au.


For more information contact:

Bart Taylor at Walker Fire Protection on 03 9279 7100 btaylor@walkerfire.com.au

Bryon Price at A.G.Coombs on 03 9248 2700 bprice@coombs-contracting.com.au

While every effort has been made to ensure the accuracy of the information in this publication A. G. Coombs assumes no responsibility for errors or omissions or for any consequences of reliance on this publication.